Journal Search Engine
ISSN : 1226-525X(Print)
ISSN : 2234-1099(Online)
ISSN : 2234-1099(Online)
Journal of the Earthquake Engineering Society of Korea Vol.18 No.1 pp.19-28
DOI : https://doi.org/10.5000/EESK.2014.18.1.019
DOI : https://doi.org/10.5000/EESK.2014.18.1.019
다양한 손상상태를 반영한 피뢰기 설비의 지진취약도 해석
Seismic Fragility Analysis of Lightning Arrester Considering Various Damage States
(Received 11 July 2013; Revised 24 September 2013; Accepted 8 October 2013)
Abstract
The seismic evaluation of electric power facilities in the switchyard of nuclear power plants is currently insufficient. In order to evaluate theseismic performance of lightning arrester subjected to four types of earthquake (near- and far-fault earthquakes, NEHRP Site Class A&Band D earthquakes), seismic fragility analysis using maximum likelihood estimation is performed considering various damage states. Thecomparison of the seismic fragility curves for three main parts of lightning arrester that are the busing, anchor and steel frame, reveals thatthe failure of lightning arrester is governed by the bushing damage mode such as porcelain cracking.
Reference

Frequency Bimonthly
Doi Prefix 10.5000/EESK
Year of Launching 1997
Publisher Earthquake Engineering Society of Korea



Online Submission
submission.eesk-j.or.kr
EESK
Earthquake Engineering Society of Korea